Physical test study on power system voltage collapse

Breadcrumb

  • Home
  • Physical test study on power system voltage collapse

Sheng Li *, Yuting Lu, Can Zhang and Yuting Zhu

School of Electric Power Engineering, Nanjing Institute of Technology, Nanjing, Jiangsu, China.
 
Research Article
Global Journal of Engineering and Technology Advances, 2022, 13(03), 001–007.
Article DOI: 10.30574/gjeta.2022.13.3.0197
DOI url: https://doi.org/10.30574/gjeta.2022.13.3.0197
Received on 17 October 2022; revised on 26 November 2022; accepted on 29 November 2022
 
In order to test and verify the phenomena of power system voltage collapse, this article chooses a single-load infinite-bus system and a single-machine single-load system as the sample systems based on the PS-5G test system to carry out the voltage stability physical tests, and an induction motor and an adjustable resistor are used to constitute the comprehensive load. The test results show that in the single-load infinite-bus system, with the decrease of the adjustable resistance gradually, the comprehensive load active power is gradually increasing and the load bus voltage is gradually decreasing; and the slight adjustment for the adjustable resistance can cause the load bus voltage collapse when the induction motor has the locked-rotor. In the single-machine single-load system, the locked-rotor of the induction motor can lead to the occurrence of the reactive power limit-induced bifurcation, it causes the terminal voltage of the synchronous generator and the load bus voltage to have an instantaneous collapse. The test results are conducive to comprehend the mechanisms of voltage instability and collapse in power systems.
 
PS-5G Test System; Voltage Collapse; Induction Motor; Synchronous Generator
 
https://gjeta.com/sites/default/files/fulltext_pdf/GJETA-2022-0197.pdf

Preview Article PDF

Sheng Li, Yuting Lu, Can Zhang and Yuting Zhu. Physical test study on power system voltage collapse. Global Journal of Engineering and Technology Advances, 2022, 13(3), 001-007. Article DOI: https://doi.org/10.30574/gjeta.2022.13.3.0197

Copyright © Author(s). All rights reserved. This article is published under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0), which permits use, sharing, adaptation, distribution, and reproduction in any medium or format, as long as appropriate credit is given to the original author(s) and source, a link to the license is provided, and any changes made are indicated.


All statements, opinions, and data contained in this publication are solely those of the individual author(s) and contributor(s). The journal, editors, reviewers, and publisher disclaim any responsibility or liability for the content, including accuracy, completeness, or any consequences arising from its use.

Get Certificates

Get Publication Certificate

Download LoA

Check Corssref DOI details

Issue details

Issue Cover Page

Editorial Board

Table of content

          

 

Copyright © 2026 Global Journal of Engineering and Technology Advances - All rights reserved

Developed & Designed by VS Infosolution